The same heating output can produce different results at different airflow rates. Moving less air means heating it to a higher temperature to carry the same amount of heat. An airflow of 26,100 m³/h carries approximately 350 kW with a temperature rise of 40 K. The examples below explain how airflow, recirculation and leakage interact. For a comparison of heat sources, see our separate guide to air dome heating options.
1. Why heating capacity alone is not enough
Heat transfer depends on both airflow and temperature difference. To deliver the same heat with less air, the temperature rise must increase. If the air-handling unit has a maximum discharge temperature, insufficient airflow can limit usable heating capacity even when the heat source has capacity to spare.
Keep three quantities separate. Thermal output, in kW, is the rate of heat transfer. Airflow, in m³/h, is the volume of air moved per hour at the stated conditions. Pressure, in Pa, describes the pressure conditions under which the system operates. Identical kW ratings do not guarantee identical performance inside a dome.
Here, heating output means heat actually transferred to the air—not fuel input or the fan motor's electrical input. Converting useful heat into purchased energy also requires the heat source's efficiency.
2. How air circulates through an air dome
The air-handling unit supplies heated air to the dome. Some escapes through leaks and other open paths to the outside. Some returns to the unit, mixes with fresh outdoor air and is heated again. This return loop is called recirculation. We distinguish three streams: outdoor air, return air and total supply air to the dome.
Air circulation diagram
An airflow of 26,000 m³/h through the unit does not necessarily mean the same volume of fresh outdoor air. With 70% outdoor air and 30% return air, the outdoor stream is 18,200 m³/h and the return stream is 7,800 m³/h. Together they make up the total supply airflow to the dome.
In steady-state operation, outdoor air must replace the air escaping to the surroundings. Recirculation adds no net air: air is taken from the dome and returned to it. A closed recirculation loop alone cannot maintain internal pressure.
Replacing leakage provides continuous air exchange. At an illustrative rate of 30 m³/h per person, an outdoor airflow of 18,200 m³/h corresponds to approximately 607 people. That is a substantial volume margin for a tennis dome with six players, so a separate ventilation system is not automatically necessary. The required rate nevertheless depends on activity, occupancy and air-quality requirements: 30 m³/h is a comparison input here, not a universal sports ventilation standard. Air distribution within the occupied zone matters too.
An exact balance uses mass flow, because a cubic metre of cold air does not weigh the same as a cubic metre of warm air. These examples compare volume flows at a common reference density.
3. How the perimeter seal affects air leakage
Floor area alone does not describe where air escapes. The membrane's connection around the dome perimeter is an important detail: the joint's length, construction and airtightness influence how much replacement air is needed.
A 60 × 40 m dome has a floor area of 2,400 m² and a 200 m perimeter. An 80 × 30 m dome has the same area but a 220 m perimeter. A longer perimeter means more joint length—not automatically a proportional increase in leakage.
The actual outdoor airflow also depends on the pressure difference, joint condition, entrances and other openings. Perimeter length alone cannot determine how much cold air needs heating. The energy balance must distinguish outdoor air replacing leakage from total airflow including recirculation.
4. Calculating the airflow needed to transfer heat
For sensible heat—heating without a change in the phase of water—the stated air properties give:
V̇ [m³/h] = P [kW] / (0.000335 × ΔT [K])
The coefficient 0.000335 includes conversion from hours to seconds. Using 0.335 would give watts, not kilowatts. A 40 K difference means a temperature rise of 40 °C, not a final air temperature of 40 °C.
| Air temperature rise ΔT [K] | Required airflow [m³/h] |
|---|---|
| 20 | 52,239 |
| 25 | 41,791 |
| 30 | 34,826 |
| 35 | 29,851 |
| 40 | 26,119 |
| 45 | 23,217 |
| 50 | 20,896 |
Chart 1. Same heat output, different temperature rises
For 350 kW and a 40 K rise, 350 / (0.000335 × 40) gives approximately 26,119 m³/h. A rise of only 20 K requires twice the airflow. At 50 K, the required flow is approximately 20,896 m³/h.
A greater temperature rise allows a smaller airflow to carry the same heat output, but the membrane and ductwork impose temperature limits. For the equipment described here, the maximum discharge-air temperature is +70 °C; the heating unit shuts down at that temperature. The membrane used in this assembly melts at +72 °C. These values apply to this assembly, not to every membrane. The shutdown temperature is not a normal operating target. Excessively hot air also rises towards the crown, increasing stratification while the playing area can remain cooler. The comparison therefore also considers a milder total supply-air temperature of +40 °C.
5. Airtightness determines the scope for recirculation
Outdoor air must first replace leakage; the recirculation fraction follows from that balance. If the dome loses 18,200 m³/h at operating pressure and total supply airflow is 26,000 m³/h, 7,800 m³/h remains available for return air: 30%. A 60% recirculation fraction is not possible at these flows, because the outdoor air would no longer replace the leakage.
Compare the same model dome size at three levels of airtightness. Total airflow remains 26,000 m³/h, temperatures are +15 °C inside and −10 °C outside, and other heat losses are 190 kW. Leakage at the required pressure changes, rather than an arbitrary damper percentage. A tighter dome requires less outdoor air, allowing return air to make up a larger share of total circulation.
Tmix = f × Toutdoor + (1 − f) × Treturn
f = outdoor-air fraction of total airflow
| Leakage = outdoor airflow [m³/h] | Total airflow [m³/h] | Recirculation | Mixed-air temperature [°C] | Outdoor-air heating [kW] | Total heating requirement [kW] |
|---|---|---|---|---|---|
| 18,200 | 26,000 | 30 % | -2.50 | 152.4 | 342.4 |
| 14,300 | 26,000 | 45 % | 1.25 | 119.8 | 309.8 |
| 10,400 | 26,000 | 60 % | 5.00 | 87.1 | 277.1 |
Chart 2. A tighter dome needs less heat
Reducing leakage from 18,200 to 10,400 m³/h raises recirculation from 30% to 60% and reduces total heating demand from 342.4 to 277.1 kW. The 65.3 kW difference comes from heating less cold outdoor air, not simply turning a damper. At the same total airflow and pressure, a higher recirculation fraction is a useful indicator of better airtightness.
The required total supply-air temperature remains +36.8 °C in all three rows. It depends on the other heat losses of 190 kW and total airflow of 26,000 m³/h: Tsupply = 15 + 190 / (0.000335 × 26,000). A tighter dome has warmer mixed inlet air, so less heating output is needed to reach the same outlet temperature.
A return-air damper that is 60% open does not mean 60% recirculated airflow. Damper position and flow fraction are different; their relationship depends on air-path resistance. With leakage of 18,200 m³/h, 60% recirculation would require total airflow of 45,500 m³/h. Opening the return path can shift the fan operating point and increase total circulation. Outdoor air must still replace leakage at the required internal pressure. Neither damper position nor drive frequency alone determines the recirculation fraction.
Recirculation is not heat recovery. Recirculation returns the air itself; heat recovery transfers heat from an outgoing stream. This balance assumes no recovery of heat from escaping air.
6. The heating load of replacing escaping air
When warm air escapes from the dome and is replaced by cold outdoor air, the heating system must make up the temperature difference:
With +15 °C inside and −10 °C outside, the difference is 25 K. Each additional 1,000 m³/h of outdoor air creates approximately 8.4 kW of heating demand. An extra 5,000 m³/h requires approximately 41.9 kW.
| Outdoor airflow [m³/h] | ΔT 15 K | ΔT 20 K | ΔT 25 K | ΔT 30 K |
|---|---|---|---|---|
| 1,000 | 5.0 | 6.7 | 8.4 | 10.1 |
| 3,000 | 15.1 | 20.1 | 25.1 | 30.2 |
| 5,000 | 25.1 | 33.5 | 41.9 | 50.3 |
| 10,000 | 50.3 | 67.0 | 83.8 | 100.5 |
Chart 3. Outdoor airflow and heating load
The same replacement airflow needs twice as much heat at a 30 K difference as at 15 K. Leakage therefore has a greater heating impact in cold weather, even if the amount of leakage does not change.
Kilowatts measure power, not energy consumption. If an additional 8.375 kW were required for ten hours, it would represent 83.75 kWh of heat delivered to the air. Purchased energy also depends on heat-source efficiency; annual consumption depends on weather and operating hours.
Reducing heat losses must always preserve safe internal pressure and adequate air exchange. The aim is not zero outdoor airflow, but an airtight dome with a controlled, effective airflow system.
Avoiding double-counting of leakage
Heat transmission through the envelope and the heating requirement for outdoor air can be calculated separately. However, an effective thermal characteristic of the entire dome derived from operating measurements may already include leakage. Adding the same component again would overstate the result.
Our article on air dome U-values and measurements explains this distinction. In the following example, other heat losses exclude outdoor-air heating, so the two components can be added.
7. Worked example: the same heating capacity, two airflow rates
For a model dome measuring 60 × 40 m, we use +15 °C indoors, −10 °C outdoors and other heat losses of 190 kW, approximately 79 W/m² of floor area, excluding outdoor-air replacement. The 190 kW is a scenario input, not a result derived solely from the dome dimensions.
Outdoor airflow remains 18,200 m³/h in both cases. The unit can deliver up to 350 kW to the air, approximately 146 W/m² of floor area. We compare total airflow rates of 20,000 and 26,000 m³/h. The +40 °C temperature is a heat-distribution comparison target, not the unit's shutdown limit; that is +70 °C for the assembly described here.
| Quantity | Value / meaning |
|---|---|
| Dimensions, floor area and perimeter | 60 × 40 m; 2 400 m²; 200 m |
| Indoor / outdoor temperature | +15 / −10 °C |
| Outdoor air | 18,200 m³/h in both cases |
| Other heat losses | 190 kW ≈ 79 W/m² of floor area; excluding outdoor-air heating |
| Maximum heat output to air | 350 kW ≈ 146 W/m² of floor area |
| Distribution comparison target | +40 °C total supply air to the dome |
| Heating-unit shutdown temperature | +70 °C discharge air |
| Other assumptions | Steady state; no heat gains or duct losses |
Heating the outdoor air to indoor temperature requires 0.000335 × 18,200 × 25 = 152.4 kW. Adding the other losses of 190 kW gives a total heating requirement of 342.4 kW. The available 350 kW covers this in both cases. The difference lies in the required total supply-air temperature.
| Result | Case A: 20,000 m³/h | Case B: 26,000 m³/h |
|---|---|---|
| Return air [m³/h] | 1,800 | 7,800 |
| Mixed-air temperature [°C] | -7.75 | -2.50 |
| Outdoor-air heating [kW] | 152.4 | 152.4 |
| Total heating requirement [kW] | 342.4 | 342.4 |
| Required total supply-air temperature [°C] | 43.4 | 36.8 |
| Theoretical heat delivered indoors at +40 °C [kW] | 167.5 | 217.8 |
| Heater output required at +40 °C [kW] | 319.9 | 370.2 |
| +40 °C supply achievable with 350 kW | Yes | No |
| Heat losses covered with supply at or below +40 °C | No | Yes |
| Operating point below the +70 °C shutdown threshold | +43.4 °C at 342.4 kW: yes | +36.8 °C at 342.4 kW: yes |
At 20,000 m³/h and a total supply-air temperature of +40 °C, the air delivers only 167.5 kW above the indoor temperature. Covering the other heat losses of 190 kW requires +43.4 °C supply air. This is below the +70 °C shutdown threshold, so the case meets the heat balance at 342.4 kW. However, if the distribution target is no more than +40 °C, 20,000 m³/h is insufficient.
At 26,000 m³/h, a total supply-air temperature of approximately +36.8 °C is sufficient at a unit output of 342.4 kW. More airflow carries the required heat at a lower temperature. Outdoor airflow and heat losses remain unchanged, so total heating demand is unchanged too.
The 217.8 kW in the table is the theoretical heat delivered within the dome at +40 °C. A 350 kW unit cannot reach that temperature at 26,000 m³/h and the stated mixed inlet temperature: it would need 370.2 kW. The achievable operating point that covers the losses is +36.8 °C at 342.4 kW. Airflow, output and temperature cannot be combined as three independent maximum values.
Both airflow rates must also be achievable at the operating pressure. A free-air rating alone does not establish that they are available when connected to the dome.
8. Airflow must be available at the actual operating pressure
A fan does not deliver one fixed airflow under all conditions. Its operating point depends on the fan curve and the resistance of the entire air path: heat exchanger, filters, ducts, bends, dampers and the dome's pressure conditions.
Maximum free-air delivery is not automatically available once the fan is connected to a dome. At the same speed, greater resistance can reduce airflow. Increasing speed may restore it, but changes electrical demand and can reach motor or fan limits.
The dome's internal positive pressure and the fan's total pressure rise are not the same quantity. The fan must also overcome air-path resistance. Static and total pressure must also be distinguished when comparing performance data.
Heat output is not fan electrical input
The fan uses electricity to move air; the heater supplies heat to it. Both are measured in kW, but describe different processes. A 350 kW heating rating therefore does not tell you how much electricity the fan motor uses.
An approximate relationship is Pel = V̇ × Δp / η, with airflow in m³/s, fan pressure rise in Pa and overall assembly efficiency expressed between 0 and 1. The result is in watts. At 26,000 m³/h, a total pressure rise of 500 Pa and efficiency of 0.60, electrical input is approximately 6.0 kW.
The 500 Pa here is an assumed fan pressure rise, not a recommended dome pressure. Actual electrical input depends on the operating point and overall efficiency.
Drive frequency as an indicator of airtightness and fan reserve
The operator sees the frequency controlling fan speed on the variable-frequency drive. If the dome maintains operating pressure at approximately 34 Hz rather than the rated 50 Hz without recirculation, the unit does not need to run at rated speed. At the same required internal pressure, damper position and comparable conditions, a lower required frequency can indicate better airtightness. It also shows fan reserve; it is not a direct measurement of leakage or recirculation percentage.
V̇ ∝ n; Δp ∝ n²; P ∝ n³
34 / 50 = 0.68; 0.68² ≈ 0.46; 0.68³ ≈ 0.31
The indicative calculation at 34 Hz gives approximately 68% of rated airflow and 31% of rated power input. An airflow of 26,000 m³/h becomes approximately 17,700 m³/h, and 6.0 kW becomes approximately 1.9 kW. This potential power reduction illustrates why reducing unnecessary leakage is preferable to continually increasing fan speed.
This cubic relationship applies to similar operating points: pressure rise also falls to approximately 46%. When maintaining the same dome pressure with changing system resistance, actual airflow and electrical input must therefore be determined from the fan curve and measurements. The 34/50 ratio does not establish 32% recirculation, particularly when the 34 Hz reading comes from operation without return air.
Speed changes must preserve both safe pressure and the required heat transfer. Sensors and control are covered in our article on air dome pressure regulation.
9. Venting an overheating dome is a different operating mode
Replacing leakage provides normal air exchange. A separate exhaust mode is used when the dome overheats. It removes warm air so cooler outdoor air can replace it. Recirculation cannot do this because it simply returns air to the same circuit.
With +30 °C inside, +20 °C outside and an exhaust-and-replacement airflow of 10,000 m³/h, approximately 33.5 kW of sensible heat is removed. At +28 °C outside, the same airflow removes only 6.7 kW. Summer solar gains for a dome with 2,400 m² of floor area can be of the order of 100 kW or more, depending on the membrane, solar exposure and geometry. This is an order-of-magnitude comparison: removing 33.5 kW offers only partial relief against such gains, not a complete overheating solution.
When indoor and outdoor temperatures are equal, air exchange alone removes no sensible heat; hotter outdoor air may add heat. Venting is therefore not air conditioning. Its effect depends on outdoor temperature and the dome's heat gains.
Exhaust operation must be coordinated with inflation-pressure control and use the components specified in the dome design—not improvised opening of emergency doors.
10. What this means for dome operation
Air dome airflow connects the air balance and the heat balance. A tighter dome needs less outdoor air to replace leakage and less heat to warm it. Greater total circulation also carries the required heat at a lower air temperature. These values apply to steady-state operation; warming up a cold dome requires more output or more time.
- Total supply airflow includes outdoor and return air. Only outdoor air replaces air escaping to the surroundings.
- Airflow and temperature difference determine heat transfer. The +70 °C shutdown temperature is not a normal heat-distribution target.
- At a 25 K temperature difference, every additional 1,000 m³/h of outdoor air adds approximately 8.4 kW of heating demand.
- At the same total airflow and internal pressure, better airtightness allows more recirculation. Damper position alone does not indicate its flow fraction.
- Airflow, pressure, output and temperatures must form an achievable operating point; drive frequency helps track changes in that point.
Air dome airflow and recirculation: frequently asked questions
Is unit airflow the same as outdoor-air supply?
No. Total airflow can include outdoor and recirculated air. In the 26,000 m³/h model with 30% recirculation, outdoor air is 18,200 m³/h and return air is 7,800 m³/h.
How much airflow is needed to transfer 350 kW of heat?
A 40 K temperature rise gives 26,119 m³/h, approximately 26,100 m³/h; the worked model rounds this to 26,000 m³/h. A different temperature rise changes the required airflow. Unit output includes outdoor-air heating, not just the other heat losses from the dome.
Why is increasing heater capacity not always enough?
If airflow is too low, transferring more heat requires a higher air temperature. Once the permitted supply temperature is reached, increasing available heater capacity alone does not remove that limit.
Does more recirculation always reduce energy use?
Leakage is the deciding factor. At the same total airflow and internal pressure, a tighter dome allows more recirculation and needs less heat for outdoor air. At 26,000 m³/h, reducing leakage from 18,200 to 10,400 m³/h raises recirculation from 30% to 60% and reduces heating demand from 342.4 to 277.1 kW. Damper position alone is not a flow fraction.
What is the heating effect of another 1,000 m³/h of outdoor air?
At a 25 K indoor-to-outdoor difference, approximately 8.4 kW of additional heating load. This is sensible heat without heat recovery, not fan electrical input or seasonal energy consumption.
How is air exchanged inside an air dome?
Outdoor air continuously replaces escaping air. Its adequacy also depends on occupancy and how the dome is used. Separate exhaust ventilation is used during overheating; recirculation does not replace the outdoor-air supply.
Air handling as part of your dome